P262 SKIP FRQ.RNG.
0.0 Hz
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
P265 MOTOR NOM.POWER
Sets the nominal power of the motor coupled with HYDROVAR, as reported in the motor
nameplate.
P265 MOTOR NOM.POWER
1.5 kW
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
Possible settings are:
HVL
Undersized motor 2
Undersized motor 1
Default
Oversized motor
2,015
0.75 kW - 1.0 hp
1.1 kW - 1.5 hp
1.5 kW - 2.0 hp
2.2 kW - 3.0 hp
2,022
1.1 kW - 1.5 hp
1.5 kW - 2.0 hp
2.2 kW - 3.0 hp
3.0 kW - 4.0 hp
2,030
1.5 kW - 2.0 hp
2.2 kW - 3.0 hp
3.0 kW - 4.0 hp
4.0 kW - 5.0 hp
2,040
2.2 kW - 3.0 hp
3.0 kW - 4.0 hp
4.0 kW - 5.0 hp
5.5 kW - 7.5 hp
3,015
0.75 kW - 1.0 hp
1.1 kW - 1.5 hp
1.5 kW - 2.0 hp
2.2 kW - 3.0 hp
3,022
1.1 kW - 1.5 hp
1.5 kW - 2.0 hp
2.2 kW - 3.0 hp
3.0 kW - 4.0 hp
3,030
1.5 kW - 2.0 hp
2.2 kW - 3.0 hp
3.0 kW - 4.0 hp
4.0 kW - 5.0 hp
3,040
2.2 kW - 3.0 hp
3.0 kW - 4.0 hp
4.0 kW - 5.0 hp
5.5 kW - 7.5 hp
3,055
3.0 kW - 4.0 hp
4.0 kW - 5.0 hp
5.5 kW - 7.5 hp
7.5 kW - 10.0 hp
3,075
4.0 kW - 5.0 hp
5.5 kW - 7.5 hp
7.5 kW - 10.0 hp
11.0 kW - 15.0 hp
3,110
5.5 kW - 7.5 hp
7.5 kW - 10.0 hp
11.0 kW - 15.0 hp
15.0 kW - 20.0 hp
4,015
0.75 kW - 1.0 hp
1.1 kW - 1.5 hp
1.5 kW - 2.0 hp
2.2 kW - 3.0 hp
4,022
1.1 kW - 1.5 hp
1.5 kW - 2.0 hp
2.2 kW - 3.0 hp
3.0 kW - 4.0 hp
4,030
1.5 kW - 2.0 hp
2.2 kW - 3.0 hp
3.0 kW - 4.0 hp
4.0 kW - 5.0 hp
4,040
2.2 kW - 3.0 hp
3.0 kW - 4.0 hp
4.0 kW - 5.0 hp
5.5 kW - 7.5 hp
4,055
3.0 kW - 4.0 hp
4.0 kW - 5.0 hp
5.5 kW - 7.5 hp
7.5 kW - 10.0 hp
4,075
4.0 kW - 5.0 hp
5.5 kW - 7.5 hp
7.5 kW - 10.0 hp
11.0 kW - 15.0 hp
4,110
5.5 kW - 7.5 hp
7.5 kW - 10.0 hp
11.0 kW - 15.0 hp
15.0 kW - 20.0 hp
4,150
7.5 kW - 10.0 hp
11.0 kW - 15.0 hp
15.0 kW - 20.0 hp
18.5 kW - 25.0 hp
4,185
11.0 kW - 15.0 hp
15.0 kW - 20.0 hp
18.5 kW - 25.0 hp
22.0 kW - 30.0 hp
4,220
15.0 kW - 20.0 hp
18.5 kW - 25.0 hp
22.0 kW - 30.0 hp
30.0 kW - 40.0 hp
P266 MOTOR NOM.VOLT.
Sets the motor nominal voltage, as reported in the motor nameplate, according to
• the chosen motor connection
• the output voltage of the HYDROVAR
8 Programming