P125 DISP.BRIGHT.
100 %
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
P130 DISP.ROTATION
This parameter enables the rotation, by 180°, of display and push buttons relative to
standard position.
P130 DISP.ROTATION
FALSE
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
P135 BACK.COMP.
P135 BACK.COMP.
NO
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
This parameter activates the Backward Compatibility mode: when set to YES, it forces
HYDROVAR to work in a multi-pump application acting and communicating as the
previous generation HYDROVAR (HV 2.015-4.220).
HVL and HV 2.015-4.220 multi-pump communication protocol are not compatible! Thus in
a multi-pump application where there is present at least one previous generation
HYDROVAR (HV 2.015-4.220), all the other HVL model shall be forced in backward
compatibility mode. For further information check the dedicated HVL Backward
compatibility Set-up and programming guide.
8.3.6 M200 CONF.INVERTER
MENU SCOPE
This submenu includes the following software parameters:
• Software
• Number of units
• Ramp settings
• Motor settings
• Frequency settings
• STC protection
P202 SOFTWARE
Shows information about the software version of the control board.
8 Programming
HVL 2.015-4.220 Installation, Operation, and Maintenance Manual
57