P04 START VALUE
G
P04 START VALUE
100%
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
This parameter defines, in percentage (0-100%) of the required value (P02 REQUIRED
VAL.), the start value after pump stops.
If P02 REQUIRED VAL. is met and there is no more consumption, then the pump stops.
The pump starts again when the pressure drops below P04 START VALUE.
Value 100% makes this parameter not effective (100%=off)!
P05 LANGUAGE
P05 LANGUAGE
English
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
This parameter selects the display language.
P06 DATE
P06 DATE
XX.XX.20XX
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
This parameter set current date.
P07 TIME
P07 TIME
HH.MM
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
This parameter set current time.
8 Programming
48
HVL 2.015-4.220 Installation, Operation, and Maintenance Manual