Manual 37259C
SPM-D11 - Synchronizing Unit
Page 70/79
© Woodward
Option
Parameter
100/400V; 1/5 A
Adjustment range
Standard
setting
Customer settings
V contr. type
THREE-STEP/ANALOG ANALOG
T
A
T
A
Volt. controller
ON/OFF ON
on
off
on
off
Volt. controllerIsol. oper.
ON/OFF OFF
on
off
on
off
Volt. controller
Ramp
1 to 99 V/s
25 V/s
Volt. controller Dead band
[1] 0.1 to 15.V, [4] 0.5 to 60.0 V
2.0 V
Volt. controllerTime pulse>
20 to 250 ms
80 ms
Volt. controller
Gain Kp
0.1 to 99.9
15.0
V control output
see table
+/-20 mA
(+/-10 V)
V control output Init.state
0 to 100 %
50 %
V control output
(max.)
0 to 100 %
100 %
V control output
(min.)
0 to 100 %
0 %
Volt. controller
Gain Kp
1 to 240
15
Volt. controller
Reset Tn
0.0 to 60.0 s
2.5 s
Volt. controller Derivat.Tv
0.00 to 6.00 s
0.00 s
Pow.fact.control
ON/OFF OFF
on
off
on
off
Pow.fact.control Set point
i0.70 to 1.00 to c0.70
1.00
Pow.fact.control Ramp
0.01 to 0.30 /s
0.01 /s
Pow.fact.control Dead band
0.5 to 25.00 %
2.5 %
Pow.fact.control Gain
Kp
0.1 to 99.9
15.0
Pow.fact.control Gain
Kp
1 to 240
15
Pow.fact.control Reset
Tn
0.0 to 60.0 s
2.5 s
Pow.fact.control Derivat.Tv
0.00 to 6.00 s
0.00 s
Power controller
ON/OFF OFF
on
off
on
off
Power controller
P max
10 to 120 %
100 %
Power controller
P min
0 to 50 %
0 %
Warm up load
Set point
5 to 100 %
20 %
Warm up load
time
0 to 600 s
15 s
Download and
open GCB
ON/OFF OFF
on
off
on
off
Power controller
P set1 =
0 to 9,999 kW
300 kW
Power controller
P set2 =
0 to 9,999 kW
500 kW
Power set point
External
ON/OFF OFF
on
off
on
off
Analog input
0 to 20 / 4 to 20 mA
0 to 20 mA
External setp.
0mA, 4mA
0 to 9.999 kW
0 kW
External setp.
20mA
0 to 9.999 kW
500 kW
Power controller
Ramp
1 to 999 kW/s
50 kW/s
Power controller Dead band=
0.1 to 25.0 %
2.5 %
Power controller
Gain Kp
0.1 to 99.9
15.0
Power controller Sens.red.
1.0 to 9.9
2.0
Power controller
Gain Kp
1 to 240
15
Power controller
Reset Tn
0.0 to 60.0 s
2.5 s
Power controller Derivat.Tv
0.00 to 6.00 s
0.00 s
Gen.active-power Monitoring
ON/AUS OFF
on
off
on
off
Power monitoring threshold
0 to 150 %
80%
Power monitoring hysteresis
0 to 100 %
20 %
Power monitoring delay time
0 to 60 s
10 s
Active power
Load-share
ON/OFF OFF
on
off
on
off
Act. load share
Factor
10 to 99 %
50 %
Reactive power
Load-share
ON/OFF OFF
on
off
on
off
React.load share
Factor
10 to 99 %
50 %