Manual 37259C
SPM-D11 - Synchronizing Unit
© Woodward
Page 45/79
Analog Controller Outputs (SPM-D11/LSXR, Settings 'ANALOG' and 'PWM')
f control output
xxxxxxx
SPM-D11/LSXR 'ANALOG'
Controller output signal
see table
This configuration screen only appears if the frequency controller is configured as
ANALOG type! The range of the analog output signal is adjusted here. To choose
between a current signal in mA or a voltage signal in V, the appropriate jumpers
must be connected to the output terminals. (see chapter "Controller Outputs" on
page 17). The following output signals are possible:
Type
Setting in above c
figuration screen
on-
Jumper
between
terminal 8/9
Adjustment
range
Adjustment
range
min.
Adjustment
range
max.
Current
+/-20mA (+/-10V)
no
+/-20mA
-20 mA
+20 mA
+/-10mA (+/-5V)
+/-10mA
-10 mA
+20 mA
0 to 10mA (0-5V)
0 to 10mA
0 mA
10 mA
0 to 20mA (0-10V)
0 to 20mA
0 mA
20 mA
4 to 20mA
4 to 20mA
4 mA
20 mA
10 to 0mA (5 to 0V)
10 to 0mA
10 mA
0 mA
20 to 0mA (10 to 0V)
20 to 0mA
20 mA
0 mA
20 to 4mA
20 to 4mA
20 mA
4 mA
Voltage
+/-20mA (+/-10V)
yes
+/-10V
-10 Vdc
+10 Vdc
+/-10mA (+/-5V)
+/-5V
-5 Vdc
+5 Vdc
+/-3V
+/-3V
-3 Vdc
+3 Vdc
+/-2.5V
+/-2,5V
-2,5Vdc
+2,5
Vdc
+/-1V
+/-1V
-1 Vdc
+1 Vdc
0 to 10mA (0- to 5V)
0 to 5V
0 Vdc
5 Vdc
0.5V to 4.5V
0,5 to 4,5V
0,5 Vdc
4,5 Vdc
0 to 20mA (0 to 10V)
0 to 10V
0 Vdc
10 Vdc
10 to 0mA (5 to 0V)
5 to 0V
5 Vdc
0 Vdc
4.5V to 0.5V
4,5 to 0,5V
4,5 Vdc
0,5 Vdc
20 to 0mA (10 to 0V)
10 to 0V
10 Vdc
0 Vdc
f control output
Level PWM 00.0V
SPM-D11/LSXR 'PWM'
PWM signal level
3.0 to 10.0 V
This configuration screen only appears if the frequency controller is configured as
PWM type! The voltage level of the PWM signal is adjusted here.
PWM-signal
Logic --------
SPM-D11/LSXR 'PWM'
PWM signal logic
positive / negative
This configuration screen only appears if the frequency controller is configured as
PWM type!
positive
........ If the controller output signal is at 100 %, the adjusted PWM level is
output continuously, at 0 % output signal the output the PWM level
is 0 V.
negative
....... If the controller output signal is at 100 %, 0 V is output continuously,
0 % output signal corresponds to the adjusted PWM level.
f control output
Init.state 000%
SPM-D11/LSXR
'ANALOG'& 'PWM'
Initial frequency controller state
0 to 100%
This parameter is the start point for the output signal when the frequency controller
parameter is configured as OFF. The percentage value relates to the range between
the minimum and maximum values that control unit can output (see below).