The SPM-D11/LSXR has various controller outputs with the following types of signal, which can be changed by
configuration as well as an external bridge/jumper.
Versions
-
Three-step controller
via the relay manager
- Controlling n/f: Parameter "
f-controller type
" = THREE-STEP
n+/f+ = relay at terminals 45/46
n-/f- = relay at terminals 47/48
- Controlling
V
: Parameter "
V-controller type
" = THREE-STEP
V+ = relay at terminals 45/46
V-- = relay at terminals 47/48
-
Analog controller output
- Control of n/f/P: Parameter "
f controller type
" = ANALOG
Current output (mA) = no external bridge/jumper necessary
Voltage output (V) = external bridge/jumper between 8/9
Connect the Controller to terminals 9/10
- Control of V/cosphi: Parameter
"V controller type
" = ANALOG
Current output (mA) = no external bridge/jumper necessary
Voltage output (V) = external bridge/jumper between 11/12
Connect the controller to terminals 12/13
-
PWM controller output
- Control of n/f/P: Parameter "
f
controller type
" = PWM
PWM output = external bridge/jumper between 8/9
Connect the controller to terminals 9/10
Connecting the Controllers
Setting: 'THREE-STEP' (Three-step controller)
A
B
Relay output
max. 250 Vac
The contactor has to be attenuated externally.
Figure 3-14: Controller - SPM-D11/LSXR - Three-step controller
Terminal Description
A
max
45 / 46
higher
2.5 mm²
47 / 48
lower
Speed / frequency controller or voltage controller
2.5 mm²