Controller
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Entering the values in the subsequent screens will change the parameters of the controller.
CAUTION
Incorrect entries may lead to wrong measuring values and result in damage to the generator!
Idle Control
Automatic idle
Running ON
Automatic no-load control
ON/OFF
ON
................ With the generator power circuit breaker open, frequency and volt-
age are controlled to the adjusted set point values in spite of the con-
troller not being enabled (see also chapter "Function" on page 20).
OFF
.............. No-load control is carried out only with controller enabled (see also
chapter "Function" on page 20).
Terminal 6
----------------
Function of terminal 6
Release control / Set point power
Release control
The controller is enabled via the discrete input on terminal 6. The
power circuit breaker is enabled separately via terminal 3 (Enable
CB). Changing the set point value is not possible.
Set point power:
The power set point value is changed by energizing terminal 6.
Enabling of the controller occurs along with enabling of the power
circuit breaker via terminal 3 (Enable CB).
Frequency Controller
The SPM-D11/LSR is equipped with a three-position controller for frequency and does not contain the following
screens. Only the screens for setting the three-position controller are available. With the extended version SPM-
D 11/LSXR, several controller output signals can be selected via the screens, which are listed by the controller
model.
f control type
--------
SPM-D11/LSXR only
Frequency controller type THREE-STEP/ANALOG/PWM
THREE-STEP
The frequency controller operates as three-step controller and is-
sues raise (f+) and lower (f-) pulses via the configured relays. Only
one of the two controllers (the frequency or the voltage controller)
can be used for relay output at a time.
ANALOG
.... The frequency controller operates as a continuous controller with an
analog output signal (mA or V).
PWM
........... The frequency controller operates as a continuous controller with a
pulse-width-modulated output signal and constant level.
Note
: The controller setting and the following screens differ, depending on which
type of controller is selected here.