Earth current (normal):
Indication as
Range
Unit
Secondary cur-
rent
Active portion I
P
Reactive portion
I
Q
(E/ER types)
.000 – 15.0
±.00 – 15
±.00 – 15.
x In
x In
x In
Primary earth
current
.000 – 999.
k000 – k999
1k00 – 9k99
10k0 – 99k0
100k – 999k
1M00 – 2M00
A
kA*
kA
kA
kA
MA
Active portion I
P
±.00 – ±999
±k00 – ±k99
±1k0 – ±9k9
±10k – ±99k
±M10 – ±M99
±1M0 – ±2M0
A
kA*
kA
kA
MA
MA
Reactive portion
I
Q
±.00 – ±999
±k00 – ±k99
±1k0 – ±9k9
±10k – ±99k
±M10 – ±M99
±1M0 – ±2M0
A
kA*
kA
kA
MA
MA
* rated current transformer >2kA
Earth voltage:
Indication as
Range
Unit
sec. Voltage
000V – 999V
V
primary voltage .000 – 999V
1K00 – 9K99
10K0 – 99K9
100K – 999K
1M00 – 3M00
KV
KV
KV
KV
MV
6.13.3
Indication of fault data
All faults detected by the relay are indicated on the front plate optically. For this purpose, the four
LEDs (L1, L2, L3, E) and the four function LEDs (I>, I>>, IE>, IE>> and
) are equipped at
MRI3. Not only fault messages are transmitted, the display also indicates the tripped protection
function. If, for example an overcurrent occurs, first the corresponding LEDs will light up. LED I>
lights up at the same time. After tripping the LEDs are lit permanently.