Woodward
Manual MRIK3-C EN
56
DOK-TD-MRIK3-C Rev. A
6.12.3
Assignment of the AR functions
The last activation of the <SELECT/RESET> key in the relay assignment mode will activate the AR
assignment mode.
The accompanied LEDs indicate which functions will be assigned to the individual protec-
tion stages for parameter setting before the 1
st
AR.
Actuation of the <+> <-> keys permits switching over between "BLOC", "TIME" or "FAST".
Here the following functions are activated or deactivated one after the other.
1) "BLOC" blocking of the protective functions.
2) "TIME" tripping of the individual protective functions with set delay time.
3) "FAST" tripping with Fast Trip function.
Actuation of the <ENTER> key with subsequent one-time entry of the pass word will store
the altered value.
Actuation of the <SELECT/RESET> key will assign the tripping function before the 1
st
AR,
one after the other to the individual protection stages.
After this adjustment the parameters are set for activation of the 1
st
AR.
The accompanied LEDs indicate which protective functions are available for parameter set-
ting for the first AR.
Actuation of the <+> <-> keys permits switching over between "YES" and "NO". "YES"
means that the selected protection function will trigger an AR.
Actuation of the <ENTER> key with subsequent one-time entry of the password will store
the altered value.
Actuation of the <SELECT/RESET> key the protective functions are, one after the other,
assigned to the first AR.
The following table shows all parameters that have to be set. After each group the setting changes
between parameter set 1 and 2.
Function
Protection step Display-indication
corresponding LED
Trip cause
I>
TIME (FAST, BLOC)
I> + tD1
before the
I>>
TIME (FAST, BLOC)
I>> + tD1
1
st
AR
IE>
TIME (FAST, BLOC)
IE> + tD1
IE>>
TIME (FAST, BLOC)
IE>> + tD1
Function
Protection step Display-indication
corresponding LED
Activation
I>
NO (YES)
SHOT + I> + tD1
of the 1
st
AR I>>
YES (NO)
SHOT + I>> + tD1
is permitted IE>
NO (YES)
SHOT + IE> + tD1
IE>>
NO (YES)
SHOT + EI>> + tD1
Function
Protection step Display-indication
corresponding LED
Trip cause
I>
TIME (FAST, BLOC)
I> + tD1
after the
I>>
TIME (FAST, BLOC)
I>> + tD1
1
st
AR
IE>
TIME (FAST, BLOC)
IE> + tD1
IE>>
TIME (FAST, BLOC)
IE>> + tD1
Function
Protection step Display-indication
corresponding LED
Activation
I>
NO (YES)
SHOT + I> + tD2
of the 2
nd
AR I>>
YES (NO)
SHOT + I>> + tD2
is permitted IE>
NO (YES)
SHOT + IE> + tD2
IE>>
NO (YES)
SHOT + EI>> + tD2