Manual MRIK3-C EN
Woodward
DOK-TD-MRIK3-C Rev. A
63
6.14
Reset
The MRI(K)3-C offers the following three ways to reset the displayed indications as well as the out-
put relay.
Manual
reset
By pressing the <SELECT/RESET> push-button for some time (about 3 seconds
External
reset
By applying aux. voltage to C8/D8
Reset via interface
By transmitting the RESET command from the Master PC.
An indication can only be reset if there is no protective function activated. (Otherwise "TRIP" re-
mains in the display).
The set parameters are not changed by the reset procedure.
6.14.1
Erasure of the Fault Memory
For erasure of the fault memory the push-button combination <SELECT/RESET> and <-> has to
be pressed for about 3 s. During the erasure procedure „wait“ is displayed.