30
DOK-TD-MRIK3-C Rev. A
5.7.5
Saving the operating assignment
If the changed function is to be saved, the <ENTER> key must be operated. The display shows
“SAV?”. If the <ENTER> key is pressed again, you are asked for the password. The display shows
”PSW?”. Pressing the next four keys will enter the password. On the display the entry is accompa-
nied by an “X” for every entered character. The standard password for the control functions is 4x <-
>. If the password has been entered correctly, the display will show “SAV”. Now the <ENTER> key
must be pressed again and kept depressed (3s) until the function to be set reappears in the dis-
play. If the entry is incorrect, the password is requested again. The display will show “PSW?” once
more. A detailed description of entering and changing the password is provided in the description
MR – digital multifunction relays in Chapter 4.4 and in this description in Chapter 3.2.
5.7.6
Remote switching on and off of the C.B.
If the operating assignment of the C.B. control was set to remote (RMOT), the C.B. control via the
front panel is blocked. By operating the <SELECT/RESET> key you will leave the operating as-
signment again. The display will show “MRIK”.
The digital input functions:
t0 = Ext. tripping immediately
t1 = Ext. tripping delayed
ON = Ext. start
t2 = Trip/restore Function are released.
Switching on and off via the serial interface are also released.
5.7.7
Switching on or off the C.B. via the front panel (LCAL)
After having selected the function (LCAL), pressing the <SELECT/RESET> key will take you to the
control mode. The display will now show the status of the circuit breaker C.B.
CB??
Position of the C.B. cannot be established as the information from the digital inputs is insuf-
ficient. At the same time the LED CB is flashing. At this stage it is important that a digital
input which has been activated for a C.B. control function must be used. (see chapter
6.12.4 and 6.12.5). A detailed function assignment for the control signals for the C.B. can
be found in Chapter 5.7.9.
ON??
The C.B. is switched off. The LED CB shows a green light. Press the <ENTER> key and
enter the password to have ON!! shown on the display.
ON!!
The C.B. can be switched on by pressing the <ENTER> key.
OFF?
The C.B. is switched on. The LED CB shows a red light. Press the <TRIP> key and enter
the password to have OFF! shown on the display.
OFF!
The C.B. can be switched off by pressing the <TRIP> key.
The graph of the procedure of operation assignment and the C.B. control function can be found in
the next Chapter 5.7.8.