![Woodward MRIK3-C Manual Download Page 14](http://html1.mh-extra.com/html/woodward/mrik3-c/mrik3-c_manual_995914014.webp)
Woodward
Manual MRIK3-C EN
14
DOK-TD-MRIK3-C Rev. A
4.1.4
Low/High
range
of the digital Inputs
The MRI(K)3-C is equipped with a wide-range power supply unit and hence the supply voltage is
freely selectable. The switching threshold of the digital inputs, however, has to be fixed in compli-
ance with the supply voltage. Two different switching thresholds can be adjusted:
Range Plug U
AB
U
AN
Low
Plugged in <= 8V
>= 10V
High
Open
<= 60V
>= 80V
Figure 4.5
: Code jumpers