Manual MRIK3-C EN
Woodward
DOK-TD-MRIK3-C Rev. A
73
Measuring errors at
higher frequencies:
70Hz – 400Hz < 0.2% / Hz
Influences on delay time:
no additional influences can be measured
For further technical data see the general description „
MR
-Multifunctional Relay“.
8.3
Setting ranges and steps
8.3.1
System
parameter
Setting
range Step
Tolerance
I
prim
IE
prim
(SEK)
0,001...50,0KA
0.001; 0.002; 0.005; 0.01; 0.02; 0.05; 0.1; 0.2
U
E>
(U
prim
/
U
SEK
)
(SEK) 1,01...6500
0.01; 0.02; 0.05; 0.1; 0.2; 0.5; 1; 2; 5; 10; 20;
50
U
E>
U
N
= 100 V:
e-n:
1 - 70 V
1:1:
1 - 120 V
1 V
1 V
5% of the setting
value or <0.5% U
N
Operating cycle counter
Setting
range Step
Tolerance
No
0 - 9999
1
Presetting for switch off power (I
2
t)
Setting
range Step
Tolerance
I²t
0 – 655 kAs
0.01; 0.02;0.05; 0.1; 0.2; 0.5; 1; 2; 5
Date and time
Setting
range Step
Tolerance
Uhr
Y = 0..99
M = 1..12
D = 1..31
h = 0..23
m = 0..59
s = 0..59
1 year
1 month
1 day
1 hour
1 minute
1 second