6.12.4
Function assignment of the digital inputs
After the setting of the AR parameter you enter the allocation of the input function to the 7 digital.
With the push-buttons <+> and <->it is possible to assign to each digital input one available logical
input function. During the setting procedure the LED “DI” lights. The display shows the number of
the DI and the assigned logical function in a short from. „1=RE“. This means that the DI No. 1 is
assigned to the function reset. The following functions are available:
NO
= No function
RE
= Reset (Display and Relay)
BL
= Protection block / trip block
P2
= Change parameter set
FR
= Ext. Trigger of the disturbance recorder
t0
= Ext. Trip immediately
t1
= Ext. Trip with time delay
ON
= Ext. switch ON
t2
= Trip/Restore
CI
= CB position supervision CB-ON
CO
= CB position supervision CB-OFF
CR
= CB ready supervision / CB spring is charged
AB
= AWE block
SY
= Synchrocheck (only AR relay)
The allocation of the functions can be the same for different digital inputs.
6.12.5
Description of the digital input function
RE = Reset (Display and relay)
With this function the relay and the display indication are reset to normal mode. The relay shows
MRIK. Are output relays set to bistabil mode the also reset.
BL = Protection block / Trip block
All active protection function are blocked during pick up conditions.
P2 = Change parameter set
When the input is activated the relay change the active parameter set from Set1 to Set 2.
FR = Ext. Trigger for the disturbance recorder
If this function is allowed it starts the disturbance recorder from a external source. During recording
the LED FR lights. If a fault record is being written, the LED FR will be alight.
t0 = Ext. Trip immediately.
This function activates directly the trip relay to switch OFF the CB. Also the alarm relay can be acti-
vated. The relays are active as long as the input is active.
t1 = Ext. Trip with time delay.
If this function activated it start a timer with a free setable delay time. After the timer elapsed the
output relay for trip will activated. Also the alarm relay can work in the same way. The relays are
active as long as the input is active.
ON = Ext. Switch ON
When this input is activated. The output relay to switch ON of the CB is activated immediately. The
output relay is activated until the relay indicates via digital input CI that the CB is ON.
t2 = Trip/Restore
This function fulfils the requirements for a manual switch ON operation. When a high level at the
assigned digital input takes place, the relay trips immediately. When the digital input is reset to low
level a counter starts and after the settable delay time (0,1s – 300s) the relay switches ON the CB