DOK-TD-MRIK3-C Rev. A
6.5.9
Fast/Time tripping by switch ON of the CB for the short
circuit
element
After switch ON the CB a pick up of the I>> element happens directly within 200 ms, it is possible
to switch OFF without time delay when this parameter is already set. (see chapter 6.5.4)
6.5.10
Pickup value for residual voltage (UE) (ER/XR-relay types)
Regardless of the preset earth current, an earth fault is only identified if the residual voltage ex-
ceeds the set reference value. This value is indicated in volt.
6.5.11
Pickup current for earth fault element (IE>)
(Similar to chapter 6.5.1)
The pickup value of MRIK3-ICE relates to times I
N
The pickup value of MRIK3-ICER
a
nd
MRIK3-ICXR relates to % I
N
.
6.5.12
WARN/TRIP changeover
A detected earth fault can be parameterized as follows. After delay time.
a) "warn" only the alarm relay trips
b) "trip" the trip relay trips and tripping values are stored.
6.5.13
Time current characteristics for earth fault element
(for E/X-relay types)
When adjusting the trip characteristics one of the following 7 abbreviations is displayed:
DEFT -
Definite Time (definite time overcurrent protection)
NINV -
Normal inverse (Type A)
VINV -
Very inverse (Type B)
EINV -
Extremely inverse (Type C)
RINV -
RI-Inverse
LINV -
Long-term
inverse
RXID -
Special purpose characteristics
The displayed text can be changed by push-buttons <+><-> . By pressing <ENTER> the required
trip characteristics is selected.
6.5.14
Tripping Time or Time Factor for the Earth Fault Element
The setting procedure outlined in chapter 5.5.3 applies
here as well.
6.5.15
Fast/Time tripping by switch ON of the CB for the earth fault low
set
element
The setting procedure outlined in chapter 5.5.4 applies here as well.