Control
Function
Block/Trip – time
Setting
range
Step
Tolerance
Trip+Block+t>
0.1...2.0 s; EXIT
0.01; 0.02; 0.05; 0.1 s
1% or
10 ms
External trip delay time
Setting
range
Step
Tolerance
DI+Trip+t>
0,1...300,0 s; EXIT
0.01; 0.02; 0.05; 0.1; 0.2; 0.5; 1.0; 2.0; 5.0;
10 s; 20 s
1% or
10 ms
External trip immediate (no parameter setting)
Setting
range
Step
Tolerance
100ms fix
time
100ms
10 ms
Trip/Restore - time
Setting
range
Step
Tolerance
DI+t
CI
+t>
0,1...300,0 s; EXIT
0.01; 0.02; 0.05; 0.1; 0.2; 0.5; 1.0; 2.0; 5.0;
10 s; 20 s
1% or
10 ms
CB failure protection
CBFP Setting
range Step
Tolerance
CB green + t>
0.1...2.0 s; EXIT
0.01; 0.02; 0.05; 0.1 s
1% or
10 ms
8.3.7
Interface
parameter
Parameter
LED *
Setting range
Step
Tolerance
RS
1 - 32
Slave-address
1
RS
2400
4800
9600
Baud-Rate
2400,
4800
RS
even
odd
no
Parity
even
odd
none
8.3.8
Parameter
for
the fault recorder
Parameter LED
Setting
range
Step
Tolerance
Number of recordings*
FR
1
3
7
2
4
8
Existing recordings to be
overwritten *
1 x 8 s (6.66s)
3 x 4 s (3.33s)
7 x 2 s (1.66s)
Existing recordings not to
be overwritten *
2 x 8 s (6.66s)
4 x 4 s (3.33s)
8 x 2 s (1.66s)
Saving of the re-
cording at the
accurence
FR P_UP
TRIP
A_PI
TEST
At actuation
At trip
After actuation
Test recording with button
<+> and <->
Pre-Trigger-time FR
0.05...8.00
Duration of the previous
event S
* All given times refer to 50 Hz (60 Hz in brackets)