36. Technical information, balanced flue
Balanced flue
Flue gas routing options
Maximum length
1)
[m]
up to
14 kW
up to
20 kW
up to
24 kW
B23
Flue in a duct and combustion air directly via the appliance (open flue)
DN 60
DN 80
45
-
25
50
21
50
B33
Flue in a duct with horizontal, concentric supply line (open flue)
DN 60
DN 80
43
50
23
50
19
50
B33
Connection to moisture-resistant flue gas chimney with horizontal concentric
connection pipe (open flue)
Calculation to EN 13384
(balanced flue chimney
manufacturer)
C13x Horizontal roof outlet through pitched roof
(room sealed – on-site dormer)
DN 60/100
DN 80/125
10
10
10
10
10
10
C33x
Vertical concentric roof outlet through pitched or flat roof, vertical concentric
balanced flue for duct installation (room sealed)
DN 60/100
DN 80/125
DN 110/160
16
17
18
14
22
25
12
26
30
C43x
Connection to moisture-resistant balanced flue chimney, maximum pipe length
from centre of boiler bend to connection 2 m
(room sealed)
Calculation to EN 13384
(balanced flue chimney
manufacturer)
C53
Connection to flue in a duct and ventilation air supply through external wall
(room sealed), 3 m ventilation air duct incl.
DN 80/125
50
50
50
C53x
Connection to flue on external wall (room sealed),
combustion air intake via external wall
DN 80/125
50
50
50
C83x
Connection to flue in a duct and ventilation air through external wall (room
sealed)
DN 80/125
50
50
50
C83x
Concentric connection to moisture-resistant flue gas chimney and combustion
air through external wall (room sealed)
Calculation to EN 13384
(balanced flue chimney
manufacturer)
C93x Flue for duct installation
Connection pipe DN 60/100, vertical DN 60
rigid
flexible
17
13
17
13
17
13
C93x Flue for duct installation
Connection pipe DN 60/100 or DN 80/125, vertical DN 80
rigid
flexible
18
14
21
17
26
22
1)
The maximum length corresponds to the total length from the appliance to the flue terminal.
For available gas fan draughts, see specification.
Note: Systems C33x and C83x are also suitable for
installation in garages.
Where necessary, adapt the installation examples to the
relevant building regulations and requirements in your
country/region. Any questions relating to the installation,
particularly regarding the provision of inspection
components and ventilation apertures (ventilation generally
required above 50 kW output) should be raised with your
local flue gas inspector prior to installation.
The specified lengths refer to concentric balanced
flues and standard flues, and apply to original Wolf
components only.
Balanced flue systems DN 60/100 and DN 80/125
are certified as single units together with Wolf gas
condensing boilers.
The following balanced flues or standard flues with
CE-0036-CPD-9169003 certification may be used:
- Flue DN 80
- Concentric balanced flue DN 60/100 and DN 80/125
- Flue DN 110
-
Concentric balanced flue (on external walls) DN 80/125
- Flexible flue DN 83
Wolf accessories are supplied with the necessary
identification labels.
Please also observe the installation information supplied
with the accessories.