84
3064816_201804
36. Technical information, balanced flue
25
22
23
24
8
4
4
5
S
S
10
16
4/
Supplementary installation instructions for balanced flue DN 80/125
As a rule, install the adaptor from balanced flue DN 60/100
to DN 80/125 (2)
vertically and always on the flue outlet
of the gas condensing boiler.
Adaptor from balanced flue
DN 60/100 to DN 80/125
Inspection piece (3)
Determine distance A. Length of balanced flue (4) must always be
approx. 100 mm longer than distance A. Always trim the flue on the
smooth side,
never
on the female connection side.
Chamfer the flue with a file after trimming.
4
9
9
Distance A
Offset
11
10
11
11
4
4
Distance A
Distance A
Flat roof:
Affix ceiling outlet (14), approx. Ø 130 mm, to the
roof cover.
Pitched roof: For (12), observe the installation instructions on the
cowl regarding roof pitches.
If an inspection port is required for the balanced flue, insert a
balanced flue with inspection port (3) (allow a length of 200 mm).
Insert roof outlet (7) into the roof from above and secure vertically
with (6) to a rafter or brickwork.
Install the roof outlet only in its original condition. Modifica
-
tions are not permissible.
When installing, slide the separator (8) fully into the female
connection. Push the next balanced flue (4) 50 mm (dim.
"S") into the female
connection of the sep-
arator and ensure it is
fully secured in this
position, e.g. with pipe
clamps DN 125 (5) or
with a locking screw
on the air side.
* Observe the installation instructions for polypropylene (PP)
flue gas systems.
Secure support bend (23)
to support rail (22)
Secondary
ventilation
*
Install all horizontal balanced
flues with > 3° fall (6 cm/m)
towards the boiler. Any con-
densate must be returned to
the appliance.
Install the centring triangles
near the end of the pipe.
15
16
220
>400
Notes:
For inspection of (3), undo and move the lock. Undo and remove the cowl for the flue pipe.
For inspection or separation (8), separate at sliding socket.
Prior to installation, wet all air supply/flue gas joints, e.g. with a soapy solution, or lubricate them using a suitable
grease without silicone.
Please
note
Bend
Offset
87°
min. 205 mm
45°
min. 93 mm
12
13
6
14
7
650
550-1050
1250
1750-2300