24. Parameter description
If parameter HG61 is changed from its factory setting (boiler sensor), the DHW
heating system will malfunction.
Parameter HG61
DHW control unit
(DHW control)
HG45
Flue gas system/DN
0 %
2.5 %
C33x / DN 60/100
0 m - 4 m
4.25 m - 16 m
C33x / DN 80/125
0 m - 4.25 m
4.25 m - 17 m
C33x / DN 110/160
0 m - 4.5 m
4.5 m - 18 m
Other balanced flue
systems (BF), diameter
Max. balanced flue, see:
Balanced flue for wall
mounted gas condensing
boilers up to 24 kW
0 m - 0.25 x BF
max
0.25 x BF
max
- BF
max
CGS-2-14/120L
HG45
Flue gas system/DN
0 %
2.5 %
5 %
7.5 %
C33x / DN 60/100
0 m - 3.5 m
3.5 m - 7 m
7 m - 10.5 m
10.5 m -
14 m
C33x / DN 80/125
0 m - 5.5 m 5.5 m - 11 m
11 m -
16.5 m
16.5 m -
22 m
C33x / DN 110/160
0 m -
6.25 m
6.25 m -
12.5 m
12.5 m -
18.75 m
18.75 m -
25 m
Other balanced flue
systems (BF), diameter
Max. balanced flue, see:
Balanced flue for wall
mounted gas condensing
boilers up to 24 kW
0 m - 0.25
x BF
max
0.25 x BF
max
-
0.5 x BF
max
0.5 x BF
max
-
0.75 x BF
max
0.75 x BF
max
- BF
max
CGS-2-20/160L
HG45
Flue gas system/DN
0 %
2.5 %
5 %
C33x / DN 60/100
0 m - 3 m
3 m - 6 m
6 m - 12 m
C33x / DN 80/125
0 m - 6.5 m
6.5 m - 13 m
13 m - 26 m
C33x / DN 110/160
0 m - 7.5 m
7.5 m - 15 m
15 m - 30 m
Other balanced flue
systems (BF), diameter
Max. balanced flue, see:
Balanced flue for wall
mounted gas condensing
boilers up to 24 kW
0 m - 0.25 x BF
max
0.25 x BF
max
- 0.5 x BF
max
0.5 x BF
max
- BF
max
CGS-2-24/200L
There is a separate setting table for each model of the CGS-2:
The excess temperature differential between the header temperature and the
boiler water temperature during header heating is selected with parameter
HG46. The boiler water temperature continues to be limited by the maximum
boiler water temperature (parameter HG22).
Parameter HG46
Excess boiler water temperature,
header
Factory setting: See table
Setting range: 0 to 20 °C
Individual setting:
_____
Based on the maximum burner hysteresis HG 01, there is a linear reduction of
the burner shutdown point after the burner start. After expiry of the hysteresis
time (HG 33), the burner switches off when the minimum switching hysteresis
is reached (HG60).
Also see parameter HG01 diagram.
Parameter HG60
Minimum burner switching hysteresis
Factory setting: See table
Setting range: 2 to 30 °C
Individual setting:
_____