17. Display module/programming unit/
installation
Either an AM display module or a BM-2 programming unit must be installed for operating the gas condensing boiler.
The BM-2 (programming unit) communicates with the
heating appliance and all connected extension mod-
ules via eBUS.
Specification:
• 3.5" colour display, 4 function keys, 1 rotary selec-
tor with pushbutton function
• microSD card slot for software update
• Central programming unit with weather-compen-
sated flow temperature control
• Time program for heating, DHW and DHW circula-
tion
The AM functions solely as a display module for the
heating appliance. Heating appliance-specific parame
-
ters and values can be programmed and displayed.
Specification:
• 3" LCD screen
• 4 quick start keys
• 1 rotary selector with pushbutton function
Please note:
• Use when BM-2 is deployed as a remote control or
in a cascade circuit
• AM is always in the heating appliance
AM
BM-2
Operating mode
Heating mode
Burner status
ON
Status
Insert the AM or BM-2 in the slot above the ON/OFF
switch (Wolf logo).
Both modules can be plugged into this slot. Further
commissioning or address assignment measures spe-
cific to the BM-2 can be found in the BM-2 installation
instructions.
Status
Betriebsart
Brennerstatus
Heizbetrieb
Softstart
Switch on the power supply/insert the fuse and turn on
the appliance ON/OFF switch.
Status
Betriebsart
Brennerstatus
Heizbetrieb
Softstart
ON/OFF switch
14:12
20.01.2015
1.5
bar
25.2
°C
1x
Heating appliance
Heating appliance
Heating/DHW mode
Pressure