36. Technical information, balanced flue
Connection to moisture-resistant flue with two or multiple draught chimneys (duct)
The requirements of DIN 18160-1 supplementary sheet 3 apply.
Notify your local flue gas inspector prior to installation.
Open flue operation only
Stainless steel duct cover
from the Wolf product
range
Polypropylene system up
to 120 °C, CE approved
Chimney
T400
Open flue and room sealed operation
1000
Duct cover from
the Wolf product
range
Chimney
T400
Polypropylene system up
to 120 °C, CE approved
Supplementary installation instructions for balanced flue DN 60/100
Determine distance A. Length of balanced flue (4) must always be
approx. 100 mm longer than distance A. Always trim the flue on the
smooth side,
never
on the female connection side.
Chamfer the flue with a file after trimming.
4
8
8
Distance A
Offset
10
9
10
10
4
4
Distance A
Distance A
Bend
Offset
87 °
min. 170 mm
45°
min. 73 mm
Flat roof:
Affix ceiling outlet (7), approx. Ø 130 mm, to the
roof cover.
Pitched roof: For (6), observe the installation instructions on the
cowl regarding roof pitches.
If an inspection port is required for the balanced flue, insert a
balanced flue with inspection port (2) (allow a length of 200 mm).
Insert roof outlet (5) into the roof from above and secure vertically
with the mounting bracket to a rafter or brickwork.
Install the roof outlet only in its original condition. Modifications
are not permissible.
Mounting bracket
6
7
5
650
550-1050
2000
Connection to flue gas chimney (examples) DN 60/100
Connection to moisture-resistant flue gas chimney B33
Install flue gas chimney connections with air apertures right beside the flue gas chimney
as shown in the diagram, so that all components of the flue gas path are surrounded
by combustion air.
The air apertures must be completely free from obstruction.
The flue gas chimney must be tested for suitability. Apply 0 Pa when calculating the
chimney draught. Obtain the connection piece from the chimney manufacturer if required,
to safeguard the connection conditions.