23. HG control parameters
Modifications must only be carried out by a recognised heating contractor or by Wolf customer service. Incorrect
operation can lead to system faults.
On the AM display module or the BM-2 programming unit, the factory setting for the HG parameters can be
reinstated in the contractor menu.
To prevent damage to the heating system, cancel night setback if outside temperatures fall below -12 °C. If this
requirement is not observed, ice may form on the flue outlet which may cause injury or material losses.
Please
note
Please
note
The control parameters can only be modified or displayed using the AM display module or BM-2 programming unit on the heat
generator. For procedures, check the operating instructions of the relevant accessories.
No.:
Designation:
Unit
Factory setting
Condensing boiler
Min:
Max:
14 kW 20 kW 24 kW
HG01 Burner switching hysteresis
°C
12
12
12
7
30
HG02 Lower burner output, heat generator, in % (fan control)
%
26
24
24
1)
100
HG03 Upper burner output, DHW (fan control)
Maximum burner output, DHW in %
%
100
100
100
1)
100
HG04 Upper burner output, heating (fan control)
Maximum burner output, heating in %
%
100
88
88
1)
100
HG07 Heating circuit pump run-on time
Heating circuit pump run-on time in heating mode
min
1
1
1
0
30
HG08 Maximum boiler water temperature, heating (applies to heating
mode) TF-max
°C
75
75
75
40
90
HG09 Burner cycle block, applies to heating mode
min
7
7
7
1
30
HG10 Heat generator eBUS address
-
1
1
1
1
5
HG12 Gas type
-
Nat.
gas
Nat.
gas
Nat.
gas
Nat.
gas
LPG
HG13 Function, input E1
Various functions can be assigned to input E1.
-
None
None
None
Var.
Var.
HG14 Function, output A1 (230 V AC)
Various functions can be assigned to output A1.
-
None
None
None
Var.
Var.
HG15 Cylinder hysteresis, switching differential during cylinder reheating
°C
5
5
5
1
30
HG16 HC pump rate, minimum
%
45
45
45
15
100
HG17 HC pump rate, maximum
%
70
70
70
15
100
HG19 Run-on time, CPP (cylinder primary pump)
min
3
3
3
1
10
HG20 Max. cylinder heating time
min
120
120
120
30/OFF 180
HG21 Minimum boiler water temperature TK-min
°C
20
20
20
20
90
HG22 Maximum boiler water temperature TK-max
°C
85
85
85
50
90
HG23 Maximum DHW temperature
°C
65
65
65
50
90
HG25 Boiler excess temperature during cylinder heating
°C
15
15
15
1
30
HG33 Burner hysteresis runtime
min
10
10
10
1
30
HG34 eBUS feed
-
Auto
Auto
Auto
OFF
ON
HG37 Pump control type (constant/linear/spread)
-
Lin.
Lin.
Lin.
Var.
Var.
HG38 Set spread, pump control (spread)
°C
15
15
15
0
40
HG39 Soft start time
min
3
3
3
0
10
HG40
System configuration (see chapter "Parameter description")
-
01
01
01
Var.
Var.
HG41 DHW circ. pump speed
%
65
75
85
15
100
HG42 Hysteresis, header
°C
5
5
5
0
20
HG43 IO reductn, default value
-
0
0
0
-5
10
HG44 GPV curve offset
%
29,6
3)
30,9
3)
30,9
3)
15
46.4
HG45 Flue length compensation
%
2.5
0
0
0
7.5
2)
HG46 Excess boiler water temperature, header
°C
6
6
6
0
20
HG60 Minimum burner switching hysteresis
°C
7
7
7
2
30
HG61 DHW control unit (warning: do not alter these settings)
-
Boiler
sensor
Boiler
sensor
Boiler
sensor
Various Various
1)
minimum boiler output
2)
for CGB-2-14 = max 2.5 %
3)
value is achieved automatically with GLV adaptation