Manual – overview of system
No.
name
description
Factory
setup
scope
F166 Dr SpecialOverT
52s
0
~
65535
F167 free
F168
Lift numbering for
IC
card service
approved
0: no card reader
1~255 Adress of elevator
0
~
255
F169 RFID call type
RFID generates
0- down calls 1- UP calls
0
~
1
F170 RFID .1-16
Floors which are only approved
with RFID:
Bit mask Interior calls 1~16
0
~
65535
F171 RFID Freig.17-32
Floors which are only approved
with RFID:
Bit mask Interior calls 17~32
0
~
65535
F172 IRFID Freig.33-48
Floors which are only approved
with RFID:
Bit mask Interior calls 33~48
0
~
65535
F173 free
F174 free
F175 Start creep speed
Start creep speed
0.006m/s
0
~
0.100
F176 free
F177 free
F178 free
F179 free
F180 Speed gain
Assignment of the nominal speed
of the lift with top values of the
analog outputs.
50.0% - 150.0%, standard 100%
100.0%
0
~
150
F181 Duplex Nr.
Number of the lift within a group:
smallest number have highest
priority (F32=3
0
~
7
F182
Steps of speedn
reduction
Number of driving-steps, which are
used for stopping (only at
Multistep-control)
0
0
~
10
F183
Speed self-
learning analogue
Speed at self learning mode
0.800m/s
0
~
1.000
F184 free
F185 free
F186
Creeping time at
start
Creeping time at start
note also F175
0.50s
0
~
10.00
Seite 62