Manual – overview of system
No.
name
description
Factory
setup
scope
F82
Sleep-Function
Setting time until control switch into Sleepmode.
(only with additional modul)
notice : Sleepmode = T in F152 + T in F82
0 = no Sleepmode
0s
0~65535s
F83
Car call mode
0: General
1: selektive door 2xSM03
1 x SM02G limited up to max 8stops
A-side: Adress 1-8, B-Side Adress 9-16!
F84
Insp. to normal
F84=1: Reset from inspection to normal mode
has to be confirmed on the handtool
F84=0 No confirmation need
0
0~1
F85
Taxi-Steuerung
F85=0: deactivated
F85=1: activated
0
0~1
F86
VIP Function
Penthousefunction and priority for hall
0: priority for hall
>0: VIP delay time
0s
0~300s
F87
Monitorin re-
levelling
Tolerance of errors for security circuit adjustable: If error
occurs the control shutoff facility after 1 to 9 error (value
F87)
for TÜV check set to „1“
1
1~9
F88
free
F89
free
F90
free
F91
free
F93
free
F94
free
F95
free
F96
free
F97
free
F98
free
F99
free
F100 free
F101 free
F102 free
F103 free
F104 free
F105 free
F106 free
F107 free
F108 free
F109 free
F110 free
F111 free
Seite 58