Manual-overview of system
No.
name
description
Factory
setup
scope
F142 free
F143 free
F144 free
F145 DC Gain
Regulation from bus tension
100,00%
80~120
F146 Pos.error Dis.
Regulation of pos distance
180mm
180~1000
F147
Monitor mot
contactor
Monitorin contactor motor
1: ON
0: OFF
1
0~1
F148 free
F149 free
F150 free
F151 free
F152
Cabin lifght /fan
delay
Caster time for cabin light/ fan after the last run
180s
0
~
65535
F153 Monitor door lock
Monitor door lock
0: OFF
1: ON
0
0~1
F154 free
F155 free
F156
Security circuit
detection
Security circuit detection
0: with add relay (only for Asia)
1: Standard only via high voltage inputs
1
0~1
F157 free
F158 free
F159 free
F160 Cancel Call mode
Cancel call permitted/ not permitted
1
0
~
1
F161
Block floor during
time
Blocking of floors
(F137,F138,F139)
0: no blocking
1: block with time F131
2: blocking with key-switch
0
~
1
F162 free
F163 USV mode
Operation with emergency supply
0: no
1: possible
0
~
1
F164 Load device type
Type of load device and ~compensation during start of
inverter
99
0
~
99
F165
Door open
selection
Door open functionality:
Bit 0: no open/close during
inspection.
Bit 1: no opening of the door
during test-operation
Bit 2: door A basic position open
at main stop
Bit 3: door A basic position open
at every stop
0
~
65535
Seite 61