1128500
WPC 2000 User Manual
3-44
Initialization, Setup, and Checkout
7.
Check to see whether the “Motor forward” LED on the WPC 2000 Main Processor board
is lit.
•
If the “Motor forward” LED is lit, go to the next step.
•
If the “Motor forward” LED is unlit, check the wiring of the Motor Forward input
connection, and correct any problems. If the LED is still unlit, call Wintriss Tech.
Support.
8.
Press both Run/Inch palm buttons on the Operator Station at the same time.
9.
Check to see whether fault code F48 appears on the LED display.
•
If F48 displays, go to the next step.
•
If F48 does not display, check to see whether the “System air pressure” LED on the
WPC 2000 Main Processor board is unlit. If the LED is unlit, check the wiring of the
system air pressure switch input and correct any problems. Press both Run/Inch palm
buttons again. If F48 still does not display, call Wintriss Tech. Support.
10.
Apply system air pressure to the press.
11.
Check to see whether the “System air pressure” LED on the WPC 2000 Main Processor
board is lit. Clear the error code on the display by pushing the Reset/Select button.
12.
Turn off the counterbalance air and bleed down the counterbalance air pressure.
13.
Press both Run/Inch palm buttons on the Operator Station at the same time. The ram
should not move, and the fault code associated with the input the counterbalance pressure
switch is connected to (normally, F51 for User 1 Input) should display.
•
If the ram does not move and the appropriate fault code appears, restore the
counterbalance air, press the Reset/Select button, and go to the next step.
•
If the ram moves and/or the appropriate fault code does not display, check the wiring of
the counterbalance air pressure switch input, and correct any problems. Push both Run/
Inch palm buttons again. If the ram still moves and/or the appropriate fault code still
does not display, call Wintriss Tech. Support.
14.
Press the Emergency Stop button on the Operator Station.
•
If fault code F13 displays, go to the next applicable test.
•
If F13 does not display, contact Wintriss Tech. Support.
If the E-stop and Top-stop circuits are not connected according to the wiring shown in
Figure 1 at the end of the manual, the fault code that displays may be different. Call
Wintriss Tech. Support for assistance.
If the E-stop and Top-stop circuits are not connected according to the wiring shown in
Figure 1 at the end of the manual, the fault code that displays may be different. Call
Wintriss Tech. Support for assistance.
NOTICE
NOTICE
Summary of Contents for wpc 2000
Page 91: ...1128500 WPC 2000 User Manual 2 64 Installation ...
Page 191: ...1128500 WPC 2000 User Manual 5 22 Troubleshooting ...
Page 209: ...1128500 WPC 2000 User Manual A 18 Extracts from OSHA and ANSI ...
Page 225: ...1128500 WPC 2000 User Manual G 6 Glossary ...
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ......
Page 235: ......
Page 236: ......
Page 237: ......
Page 238: ......
Page 239: ......
Page 240: ......
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 246: ......
Page 247: ......
Page 248: ......
Page 249: ......
Page 250: ......