AutoSet User Manual
1137200
Installation
2-21
3.
Run wiring from the remote reset switch through flexible, liquid-tight conduit to the
bottom left knockout on the AutoSet enclosure or to the appropriate location on your
console. Measure and cut the cable so it reaches TB101B or TB101A easily.
The AutoSet control enclosure is rated NEMA 12 (protected against dust and oil). If you
ordered the enclosure, you must use conduit rated NEMA 12 and make proper conduit
connections to ensure NEMA 12 protection.
4.
Remove the connector from the TB101B or TB101A terminal block, and connect the
wires from the remote reset switch to the Remote Reset and Ground terminals as shown in
Table 2-7.
Refer to Figure 2-7, page 2-9 if you need help connecting the wires to the terminals.
Make sure not to wire the connector backwards.
5.
Plug the connector back into the TB101B or TB101A terminal block. The connector can
be plugged in only one way. Check the wiring connections to make sure they are correct.
Wiring an Oscilloscope
You can connect an oscilloscope to the AutoSet load analyzer to view or plot tonnage
waveforms produced at each strain link. The AutoSet outputs for this function are -4.688 to
+4.688 Vdc.
At 120% of press capacity, output of each strain link is 4.688 Vdc. Output is ratiometric, so at
100% of press capacity, output of each strain link is 3.907 Vdc.
For example, for an AutoSetPAC 1504+ unit with press capacity of 100 tons, the output for
each strain link is 3.907 Vdc at 25 tons of load, 1.563 Vdc at 10 tons, etc.
Follow these steps to connect an oscilloscope.
1.
Open the cover of the AutoSet enclosure, and locate terminal block TB101B (AutoSet
1500 and 1500 Plus) or TB101A (AutoSet 1504 or 1504 Plus) at the lower left of the
AutoSet processor board, referring to Figure 2-4 or Figure 2-5.
2.
Run wiring from the oscilloscope through flexible, liquid-tight conduit to the bottom left
knockout on the AutoSet enclosure or to the appropriate location on your console.
Measure and cut the cable so it reaches TB101B or TB101A easily.
The AutoSet control enclosure is rated NEMA 12 (protected against dust and oil). If you
ordered the enclosure, you must use conduit rated NEMA 12 and make proper conduit
connections to ensure NEMA 12 protection.
Table 2-7. Remote Reset Switch Wiring Connections, TB101B or TB101A
AutoSet Model
Terminal Block
Pin #
Label
1500 or 1500 Plus
TB101B
1
Remote Reset
5
Ground
1504 or 1504 Plus
TB101A
1
Remote Reset
10
Ground