1137200
AutoSet User Manual
5-2
Troubleshooting
To clear the fault, press the RESET button (standard AutoSet) or turn the DISPLAY switch to
the RESET position (AutoSet Plus). Press the RESET button or hold the DISPLAY switch at
the RESET position only briefly (i.e., less than two seconds). Otherwise, AutoSet will
recalculate setpoints.
When you reset the load analyzer, displays will stop flashing, and the “HI,” “rEP,” or “Err”
message will disappear from the Setpoints display(s), being replaced by the setpoint value.
The tonnage value(s) at fault will remain in the Load displays until the press takes the next
stroke or power is turned off.
The four types of fault conditions are described below.
High Tonnage Faults
AutoSet displays a high tonnage fault when the tonnage on one or more strain link inputs
exceeds the high tonnage setpoint. A high tonnage fault is indicated on the front panel as
follows (see Figure 5-1):
HOLD THE RESET BUTTON OR DISPLAY SWITCH FOR LESS THAN TWO SECONDS
If you press the RESET button (standard AutoSet) or hold the DISPLAY switch at the RESET
position (AutoSet Plus) for more than two seconds, AutoSet will recalculate setpoints instead of
resetting the fault.
Figure 5-1. AutoSet 1504 Plus Front Panel Displaying High Setpoint Faults
NOTICE
RIGHT
LEFT
ZERO CAM
REAR LOAD
SETPOINTS
SETPOINTS
FRONT LOAD
TOTAL
Flashing tonnage
value on channels
at fault
Flashing HI
message on
channels at fault
Flashing Total
tonnage value
(AutoSet 1504 only)
DISPLAY
HIGH
RESET
REPEATABILITY
REVERSE
AutoSet 1504
®
WINTRISS LOAD ANALYZER
PLUS