1137200
Operation
4-11
d. When you have determined the correct repeatability setting, set the “% TOL” indicator
dial to approximately twice that value.
5.
If AutoSet stops the press after the new setpoints have been calculated due to a high
tonnage fault (indicated by a flashing channel Load display and the abbreviation “HI”
appearing in the corresponding Setpoints display), do the following:
a. Establish that the press stopped due to low setpoints by checking for malfunctions
such as a stuck part, load imbalance, misfeed, etc.
b. If the press stopped because high tonnage setpoints were too low, turn the “% TOL”
indicator dial up to position 5 (i.e., 20%), turn the “% REP” dial down to position 3
(i.e., 3%), and repeat steps 2 and 3.
c. If AutoSet stops the press due to a repeatability fault but displays no high tonnage
error, turn the “% REP” dial back to position 4 (i.e., 5%), and repeat steps 2 and 3. If
AutoSet stops the press, turn the “% REP” dial up to the next higher setting. Continue
this process until you get no more repeatability faults.
d. If AutoSet stops the press due to a high tonnage fault but displays no repeatability
error, turn the “% TOL” dial up to position 6 (i.e., 25%), and repeat steps 2 and 3. If
AutoSet stops the press, turn the “% TOL” dial up to the next higher setting. Continue
this process until you get no more high tonnage faults.
6.
If AutoSet stops the press after the new setpoints have been calculated due to both a
repeatability and high tonnage fault (indicated by a flashing channel Load display and the
abbreviations “rEP” and “HI” appearing alternately in the corresponding Setpoints
display), do the following:
a. Establish that the press stopped due to low setpoints by checking for malfunctions
such as a stuck part, load imbalance, misfeed, etc.
b. If the press stopped because repeatability and high tonnage setpoints were too low,
turn the “% REP” indicator dial up to position 5 (i.e., 7%), turn the “% TOL” dial also
up to position 5 (i.e., 20%), and repeat steps 2 and 3.
c. If AutoSet stops the press due to a repeatability fault but displays no high tonnage
error, turn the “% REP” dial up to position 6 (i.e., 10%), and repeat steps 2 and 3. If
AutoSet stops the press, turn the “% REP” dial up to the next higher setting. Continue
this process until you get no more repeatability faults.
d. If AutoSet stops the press due to a high tonnage fault but displays no repeatability
error, turn the “% TOL” dial up to position 6 (i.e., 25%), and repeat steps 2 and 3. If
AutoSet stops the press, turn the “% TOL” dial up to the next higher setting. Continue
this process until you get no more repeatability faults.
e. If AutoSet stops the press due to both a repeatability and high tonnage fault, turn the
“% REP” dial up to position 6 (i.e., 10%), turn the “% TOL” dial up to position 6 (i.e.,
25%), and repeat steps 2 and 3. If AutoSet stops the press due to a repeatability or
high tonnage fault, perform step 6c or 6d. If AutoSet stops the press due to both a
repeatability and high tonnage fault, turn the “% REP” and “% TOL” dials up to the
next higher setting. Continue this process until you get no more repeatability and high
tonnage faults.