ActiveScale™ P100 Support Guide
47
To program a System Interconnect:
1. Obtain the correct System Interconnect configuration file for your system from Western Digital
Corporation support.
2. Edit the System Interconnect configuration file as follows:
a. Modify the IP address for the syslog target to match your environment.
b. Modify the IP address for VLAN to match your environment.
c. Modify the time and time zone to match your environment.
3. Connect your computer to the Ethernet
port on the System Interconnect.
4. Configure your computer manually to be on the same network as the System Interconnect with the
following values:
– Management Port:
192.168.123.0/24
– Subnet:
255.255.255.0
– Gateway:
192.168.123.123
5. Open a
Telnet
session to the replacement System Interconnect and replace
switchport_IP
with
the default IP address
192.168.123.123
.
The System Interconnect command prompt appears.
6. Log in using the default credentials (user name admin, no password).
7. Type
enable
to enter the Privileged EXEC command mode.
8. Type
configure
to enter the Privileged CONF command mode.
9. Configure the name of the switch.
Replace
DC01
with the data center index you use for this data center. Replace
SW01
with
SW02
if
you are replacing the upper System Interconnect.
The prompt changes to the new name of the switch.
10. Copy the entire contents of your modified System Interconnect configuration file, and paste it into the
telnet session.
11. Save the new configuration.
This operation may take a few minutes. Management interfaces are not available during this time.
(
Routing
)>
enable
(
Routing
)#
configure
(
Routing
) (
Config
)#
(
Routing
) (
Config
)#
DC01-SW02
(
DC01-SW02
) #
(DC01-SW02) #write memory
Are you sure you want to save? (y/n) y
Config file 'startup-config' created
successfully. Configuration Saved!
Summary of Contents for ActiveScale P100
Page 103: ...ActiveScale P100 Support Guide 101...
Page 104: ...ActiveScale P100 Support Guide 102...
Page 120: ...ActiveScale P100 Support Guide 118...
Page 124: ...ActiveScale P100 Support Guide 122...
Page 131: ...ActiveScale P100 Support Guide 129...
Page 132: ...ActiveScale P100 Support Guide 130...