WattMaster WHP
Section 4
4-42
Start-Up and Troubleshooting
5.6 Pressure Sensor Voltage Chart
PRESSURE
PSI
CURRENT
MILIAMPS
VOLTAGE AT
INPUT
VDC*
0
4.00
1.00
1
4.32
1.08
2
4.64
1.16
3
4.96
1.24
4
5.28
1.32
5
5.60
1.40
6
5.92
1.48
7
6.24
1.56
8
6.56
1.64
9
6.88
1.72
10
7.20
1.80
11
7.52
1.88
12
7.84
1.96
13
8.16
2.04
14
8.48
2.12
15
8.80
2.20
16
9.12
2.28
17
9.44
2.36
18
9.76
2.44
19
10.08
2.52
20
10.40
2.60
21
10.72
2.68
22
11.04
2.76
23
11.36
2.84
24
11.68
2.92
25
12.00
3.00
26
12.32
3.08
27
12.64
3.16
28
12.96
3.24
29
13.28
3.32
30
13.60
3.40
31
13.92
3.48
32
14.24
3.56
33
14.56
3.64
PRESSURE
PSI
CURRENT
MILIAMPS
VOLTAGE AT
INPUT
VDC*
34
14.88
3.72
35
15.20
3.80
36
15.52
3.88
37
15.84
3.96
38
16.16
4.04
39
16.48
4.12
40
16.80
4.20
41
17.12
4.28
42
17.44
4.36
43
17.76
4.44
44
18.08
4.52
45
18.40
4.60
46
18.72
4.68
47
19.04
4.76
48
19.36
4.84
49
19.78
4.92
50
20.00
5.00
*Notes
:
1.
Use the voltage column to compare the
meter voltage with the sensor connected to
the controller and with the controller pow-
ered.
2.
Read voltage with meter set on DC volts.
Place the “-”(minus) lead on GND terminal
and the “+”(plus) lead on the sensor input
terminal being investigated.
3.
If the voltage is less than 0.05 VDC, then
the sensor or wiring is “shorted” or “open”
Summary of Contents for Water Source Heat Pump
Page 1: ...WHP Water Source Heat Pump Design Installation Operations Manual Revision 02A...
Page 2: ......
Page 4: ......
Page 6: ......
Page 22: ...Section 1 WattMaster WHP 1 16 Design Guide Notes...
Page 48: ......
Page 80: ...Section 3 WattMaster WHP 3 32 Programming Notes...
Page 125: ...WattMaster WHP Section 4 Start Up and Troubleshooting 4 43 Notes...