WattMaster WHP
Section
3
Programming
3-7
Status Screen #6
Note:
If no alarms exist, then the screen displays the message shown for No Alarms!
If ANY alarm exists then the three lines display one of the messages shown
above.
The Cooling Failure and Heating Failure alarms are generated as follows:
As the unit enters the cooling mode, the current Supply Air Temperature reading
is stored in memory. After 10 minutes, if the temperature hasn’t changed by 5
°
F a
Cooling Failure alarm is generated.
A Heating Failure is generated in the same manner, only during the heating mode
instead of the cooling mode.
The Hi Space Temp and Lo Space Temp Alarms are generated as follows:
If the space temperature gets 5
°
F above the cooling setpoint, a Hi Space Temp
Alarm is generated. If the space temperature gets 5
°
F below the heating setpoint,
a Lo Space Temp Alarm is generated.
Line 2 -
Bad Space Sensor
Hi Space Temp Alarm!
Lo Space Temp Alarm!
Space Temp Sensor OK
Line 3 -
Dirty Filter Alarm
Filter OK
Line 4 -
Cooling Failure!
Heating Failure!
WSHPRV 1 V2.03
Space Temp Sensor OK
Filter OK
Cooling Failure
Summary of Contents for Water Source Heat Pump
Page 1: ...WHP Water Source Heat Pump Design Installation Operations Manual Revision 02A...
Page 2: ......
Page 4: ......
Page 6: ......
Page 22: ...Section 1 WattMaster WHP 1 16 Design Guide Notes...
Page 48: ......
Page 80: ...Section 3 WattMaster WHP 3 32 Programming Notes...
Page 125: ...WattMaster WHP Section 4 Start Up and Troubleshooting 4 43 Notes...