WattMaster WHP
Section
3
Programming
3-15
Setpoint Screen #5
Setpoint Screen #6
Setpoint Screen #7
WHP #1 Setpoints
Min Run Time: x Min
Min Off Time: x Min
Min Cycle...:xx Min
The Min Run Time determines how long the compressor
must remain on once it has been activated. The Min Off Time
determines how long the compressor must remain off once it
is de-activated. The Min Cycle time determines how many
times per hour the compressor can be started. If you entered
10 minutes, the compressor could start a maximum of 6 times
in a one hour period.
Minimum
Default
Maximum
Min Run Time
0 Min
1 Min
20 Min
Min Off Time
0 Min
6 Min
20 Min
Min Cycle
0 Min
12 Min
60 Min
WHP #1 Setpoints
Changeover Delay
Between Heat/Cool
Modes......:xx Min.
To prevent rapid cycling between heating and cooling modes,
you can enter a time period that must be satisfied before the
changeover can occur.
Minimum
Default
Maximum
Changeover Delay
1 Min
30 Min
60 Min
WHP #1 Setpoints
Enable Signal Select
NO ENABLE REQUIRED
Use Left/Right Arrow
Normally you would want to have an Enable Signal that gave
assurance of water flow before you activate the heat pumps
compressor. If you need to operate without this enable signal,
use the arrow keys to select the NO ENABLE REQUIRED
message. Otherwise, select the LOOP FLOW REQUIRED
message so that the signal must be present for the compressor
to run.
Summary of Contents for Water Source Heat Pump
Page 1: ...WHP Water Source Heat Pump Design Installation Operations Manual Revision 02A...
Page 2: ......
Page 4: ......
Page 6: ......
Page 22: ...Section 1 WattMaster WHP 1 16 Design Guide Notes...
Page 48: ......
Page 80: ...Section 3 WattMaster WHP 3 32 Programming Notes...
Page 125: ...WattMaster WHP Section 4 Start Up and Troubleshooting 4 43 Notes...