WattMaster WHP
Section
3
Programming
3-17
Setpoint Screen #11
Setpoint Screen #12
Setpoint Screen #13
If your system is configured to use the reversing valve and
you only have one stage of heating and cooling, that last
relay becomes available for other uses. The AUXILIARY
RELAY MODE can be used to operate the relay manually
from the Prism computer front end program. If you select
ISOLATION VALVE MODE, the relay activates anytime
the compressor is called for or whenever the Loop Controller
sends an override command to activate and reduce loop
pressure.
If the relay needs to follow an external week schedule, select
the AUXILIARY RELAY MODE and then see the Aux
Relay #5 Schedule assignment screen.
WHP #1 Setpoints
Relay5 Configuration
AUXILIARY RELAY MODE
Use Left/Right Arrow
WHP #1 Setpoints
Fan Mode of Op
RUNS CONTINUOUS MODE
Use Left/Right Arrow
You can program the fan to run continuously during the
occupied mode,
(
RUNS CONTINUOUS MODE
)
or you
can program it to cycle on and off with the compressor
during both the occupied and the unoccupied mode of
operation.
(CYCLES W/COMPRESSOR)
WHP 1# Setpoints
Aux Relay #5 Uses
Uses Schedule #: x
0) None 1-7) Clock
If you configured relay #5 as an Auxiliary Relay, you can
also program it to follow an external schedule command.
You must have an OSS Optimal Start Scheduler installed
somewhere on you communications loop to provide the
external schedule you select here.
Summary of Contents for Water Source Heat Pump
Page 1: ...WHP Water Source Heat Pump Design Installation Operations Manual Revision 02A...
Page 2: ......
Page 4: ......
Page 6: ......
Page 22: ...Section 1 WattMaster WHP 1 16 Design Guide Notes...
Page 48: ......
Page 80: ...Section 3 WattMaster WHP 3 32 Programming Notes...
Page 125: ...WattMaster WHP Section 4 Start Up and Troubleshooting 4 43 Notes...