WattMaster WHP
Section
3
Programming
3-27
Loop Controller Setpoints
Loop Controller Setpoint Menu
Setpoint Screen #1
Setpoint Screen #2
1)
LC Setpoints
2)
LC Schedules
3)
LC Force Modes
ESC) To Exit
If the controlling water temperature rises above this Setpoint,
the Heat Rejection or Cooling Stages begin to stage on. As the
temperature continues to rise above the Setpoint by the
Deadband amount, an additional stage is added. Each
additional stage can only activate if the temperature rises above
the Setpoint by the number of active stages times the deadband
value.
Example: There are 2 stages on, a 3
°
deadband and the setpoint
is 79
°
2 x 3
°
+ 79
°
= 85
°
before stage 3 can activate
WHP Loop Setpoints
HEAT REJECTION
Setpoint......: xx
°
F
Stage Deadband: xx
°
F
Minimum
Default
Maximum
Setpoint
50
°
F
79
°
F
99
°
F
Stage Deadband
1
°
F
3
°
F
10
°
F
WHP Loop Setpoints
HEAT REJECTION
Stage Delay...: x M
The Staging Delay period must also be satisfied before an
additional stage of cooling or heat rejection can be activated.
The maximum number of heat rejection stages are programmed
on this screen also.
Minimum
Default
Maximum
Stage Delay
1 Minute
1 Minute
60 Minutes
Summary of Contents for Water Source Heat Pump
Page 1: ...WHP Water Source Heat Pump Design Installation Operations Manual Revision 02A...
Page 2: ......
Page 4: ......
Page 6: ......
Page 22: ...Section 1 WattMaster WHP 1 16 Design Guide Notes...
Page 48: ......
Page 80: ...Section 3 WattMaster WHP 3 32 Programming Notes...
Page 125: ...WattMaster WHP Section 4 Start Up and Troubleshooting 4 43 Notes...