WattMaster WHP
Section 4
Start-Up and Troubleshooting
4-33
5.3.9
Checking the Local Loop at a WHP Controller
Diagram
Meter Set To Read DC Volts
The indicated readings are typical of a normal operating system. Actual readings may vary
slightly due to the number of units installed and other factors. Any significant deviation
from these values generally indicates a problem.
Note: These tests assume that a MiniLink is connected and powered up.
Overview
Proper loop voltages are essential for reliable communications. It is normal to see fluctua-
tions on an operating communications loop. The average value should be close to the ac-
ceptable range described below. Values will vary upon initial powerup for about 30-45 sec-
onds. The voltages may fluctuate as normal communications occur.
Measurements
Local Loop
Acceptable Range
T – SHLD
2.9 - 3.1 Volts DC
R – SHLD
1.9 - 2.1 Volts DC
Action
Condition
Action
If meter reads between 2.4 VDC and 2.5
VDC
The Comm Loop “floats” at 2.4 - 2.5VDC
when only controllers are connected to the
loop. When a MiniLink is connected it will
“bias” each side of the loop to the values
listed above.
1) No CommLink II or MiniLink is con-
nected and powered up.
2) If a CommLink II or MiniLink is con-
nected, look for “open” wiring.
If voltages are too high or too low on either
side
One or more devices connected to this loop
have damaged Comm Driver chips.
Summary of Contents for Water Source Heat Pump
Page 1: ...WHP Water Source Heat Pump Design Installation Operations Manual Revision 02A...
Page 2: ......
Page 4: ......
Page 6: ......
Page 22: ...Section 1 WattMaster WHP 1 16 Design Guide Notes...
Page 48: ......
Page 80: ...Section 3 WattMaster WHP 3 32 Programming Notes...
Page 125: ...WattMaster WHP Section 4 Start Up and Troubleshooting 4 43 Notes...