WattMaster WHP
Section 2
Installation and Wiring
2-5
The daisy chain is the best method for running a communications loop since there is only
one starting point and one ending point for each of the communications loops. Even
though the daisy chain configuration is preferred, the star configuration can also be used.
If required, a combination of the two can also be used. Remember, the best
communication loop wiring is the one which utilizes the minimum number of ends while
using the shortest wiring path.
Note:
The loop does not have to follow the controller address sequence.
Caution:
If the comm loop is not installed in conduit, be careful to position the
cable away from high noise devices like fluorescent lights, transformers,
VFD’s, etc. Conduit is not required for comm loop wiring unless
required by local codes.
Make sure CommLink jumper is set for “Multi”.
Summary of Contents for Water Source Heat Pump
Page 1: ...WHP Water Source Heat Pump Design Installation Operations Manual Revision 02A...
Page 2: ......
Page 4: ......
Page 6: ......
Page 22: ...Section 1 WattMaster WHP 1 16 Design Guide Notes...
Page 48: ......
Page 80: ...Section 3 WattMaster WHP 3 32 Programming Notes...
Page 125: ...WattMaster WHP Section 4 Start Up and Troubleshooting 4 43 Notes...