WattMaster WHP
Section 4
4-22
Start-Up and Troubleshooting
5.1.2
General Troubleshooting Checklist
Begin troubleshooting by locating the general problem in the list below. Detailed
component troubleshooting information follows later in this section.
Zone is too warm
•
Is zone calling for cooling?
•
Is the compressor disabled due to minimum off time setting?
•
Is water proof of flow signal disabled?
•
Is the LED blinking an error code? See Figure 4-6.
Zone is too cool
•
Is zone calling for heating?
•
Is the compressor disabled due to minimum off time setting?
•
Is water proof of flow signal disabled?
•
Is the LED blinking an error code? See Figure 4-6.
Zone Sensor reading incorrectly
•
Is the sensor near a source of heat or a cold draft? Location is a common problem.
The sensor should be mounted on an inside wall away from heat sources and in a
location with adequate room air circulation.
•
Is the resistance reading correct? Check with the Temperature/Resistance Chart in
this section. (see page 4-42)
•
Is wiring correct? Check for errors.
Check the Room sensor
•
To meter the Room sensor:
Unplug the room sensor terminal block. Using your meter, check the resistance of the
unplugged terminal block. Use the supplied Temperature/Resistance Chart (page 4-
42) to see if the sensor is within a reasonable range. Readings which are much too
high or too low generally indicate wiring problems.
•
To meter the Slide Adjust (optional):
Use your ohmmeter to check the resistance between the room sensor GND wire and
the AIN2 terminal on the unplugged terminal block.
The resistance for various positions of the slider on the sensor should be as follows:
Full UP position
15K
Ω
(
±
500
Ω
)
MID position
12.5K
Ω
(
±
500
Ω
)
Full DN position
10K
Ω
(
±
500
Ω
)
Summary of Contents for Water Source Heat Pump
Page 1: ...WHP Water Source Heat Pump Design Installation Operations Manual Revision 02A...
Page 2: ......
Page 4: ......
Page 6: ......
Page 22: ...Section 1 WattMaster WHP 1 16 Design Guide Notes...
Page 48: ......
Page 80: ...Section 3 WattMaster WHP 3 32 Programming Notes...
Page 125: ...WattMaster WHP Section 4 Start Up and Troubleshooting 4 43 Notes...