Section 3
WattMaster WHP
3-14
Programming
Setpoint Screen #2
Setpoint Screen #3
Setpoint Screen #4
WHP #1 Setpoints
Unoccupied Setpoints
Cool Setup.: xx
°
F
Heat SetBk.: xx
°
F
The Unoccupied Heating and Cooling Setbacks are programmed
on this screen. The Cooling SetUp is added to the Occupied
Cooling Setpt to create the Unoccupied Cooling Setpoint. The
Heating SetBack is added to the Occupied Heating Setpt to
create the Unoccupied Heating Setpt.
Minimum
Default
Maximum
Cool SetUp
1
°
F
10
°
F
30
°
F
Heat SetBack
-1
°
F
-10
°
F
-30
°
F
WHP #1 Setpoints
Slide Effect: x
°
F
SP Deadband.: xx
°
F
OV Duration.:x.x Hr
If the Space Temperature Sensor has the optional slide
adjustment, then the Slide Effect is the maximum amount of
change that it can have on the Heating and Cooling Setpoint and
it is programmed here.
The SP Deadband is divided in half across the current heating
and cooling setpoint, and is used in staging the heating and
cooling on or off.
If you have an override pushbutton on the space sensor, the OV
Duration is the length of time the unit will be in the occupied
mode after pushing the button
Minimum
Default
Maximum
Slide Effect
0
°
F
3
°
F
5
°
F
SP Deadband
0
°
F
1
°
F
20
°
F
OV Duration
0.0 Hr
1.0 Hr
8.0 Hr
WHP #1 Setpoints
Cooling Stages: x
Heating Stages: x
If the Heat Pump is configured to operate with a Reversing
Valve, relay #5 can be configured as a second stage for either
heating or cooling or both. If the Heat Pump is configured for
individual heating and cooling, this determines how many of
each stage there are.
Minimum
Default
Maximum
Cooling Stages
0
1
2
Heating Stages
0
1
2
Summary of Contents for Water Source Heat Pump
Page 1: ...WHP Water Source Heat Pump Design Installation Operations Manual Revision 02A...
Page 2: ......
Page 4: ......
Page 6: ......
Page 22: ...Section 1 WattMaster WHP 1 16 Design Guide Notes...
Page 48: ......
Page 80: ...Section 3 WattMaster WHP 3 32 Programming Notes...
Page 125: ...WattMaster WHP Section 4 Start Up and Troubleshooting 4 43 Notes...