Auto-Zone Plus
Section 4
Start-Up and Troubleshooting
4-11
1.3.4
Checking the Zone Manager Network Loop
Diagram
Meter Set To Read DC Volts
The indicated readings are typical of a
normally
operating system. Actual readings may vary
slightly due to the number of units installed and other factors. Any significant deviation
from these values generally indicates a problem.
Note:
These tests assume that the CommLink II is connected and powered, and that all
Zone Managers which are connected are also powered.
Overview
Proper loop voltages are essential for reliable communications. It is normal to see
fluctuations on an operating communications loop. The
average
value should be close to the
acceptable range described below.
Values will vary upon initial powerup for about 15-30
seconds as normal communications occur
.
Measurements
LOCAL LOOP
Acceptable Range
T - G (SHLD)
2.9 - 3.1 Volts DC
R - G (SHLD)
1.9 - 2.1 Volts DC
firealarmresources.com
Summary of Contents for Auto-Zone Plus
Page 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 116: ...firealarmresources com...
Page 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Page 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Page 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Page 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...