Auto-Zone Plus
Section 1
Design Guide
1-17
Round Dampers
Table 1-1:
Round Air Damper Selection
Rectangular Dampers
Table 1-2:
Rectangular Damper Selection
Round Air Damper Selection
Air Damper Round Duct Size
( Area Ft
2
)
6”
(0.188)
8”
(0.338)
10”
(0.532)
12”
(0.769)
14”
(1.050)
16”
(1.375)
Velocity Through Round Air
Damper
(FPM)
Volume Through Round Air Damper
(CFM)
750 -
Zone
141
254
399
577
788
1031
1000 -
Zone
188
338
532
769
1050
1375
1250 -
Zone
235
423
665
961
1313
1718
1500 -
Zone
282
507
798
1154
1575
2062
1750 -
Bypass Only
329
592
931
1346
1838
2405
2000 -
Bypass Only
376
676
1064
1538
2100
2749
2250 -
Bypass Only
423
761
1197
1730
2363
3094
Rectangular Damper Selection
Damper
Height
(B)
8”
10”
12”
14”
16”
18”
20”
22”
24”
26”
28”
30”
32”
34”
36”
Damper
Width
(A)
Airflow Through Rectangular Damper
CFM @ 1000 FPM Velocity
8”
410
530
640
740
850
970
1080
1190
1300
1410
1520
1630
1740
1850
1970
10”
510
590
690
800
910
1030
1150
1260
1380
1500
1610
1730
1840
2000
2080
12”
560
650
730
850
970
1090
1210
1330
1460
1580
1700
1820
1940
2060
2190
14”
660
770
880
1030
1180
1330
1480
1630
1760
1910
2060
2210
2360
2510
2640
16”
750
890
1030
1200
1370
1540
1710
1880
2060
2230
2400
2570
2740
2910
3090
18”
770
980
1180
1380
1580
1780
1980
2180
2350
2550
2750
2950
3150
3350
3540
20”
850
1090
1330
1550
1770
1990
2210
2430
2650
2870
3090
3310
3530
3750
3990
22”
930
1210
1480
1730
1980
2230
2480
2730
2950
3200
3450
3700
3950
4200
4440
24”
950
1290
1630
1900
2170
2440
2710
2980
3250
3520
3790
4060
4330
4600
4880
26”
990
1390
1780
2080
2380
2680
2980
3280
3550
3850
4150
4450
4750
NA
NA
28”
1070
1500
1930
2250
2570
2890
3210
3530
3850
4170
4500
4820
NA
NA
NA
30”
1020
1550
2080
2430
2780
3130
3480
3830
4150
4500
4850
NA
NA
NA
NA
32”
1090
1660
2230
2600
2970
3340
3710
4080
4450
4820
NA
NA
NA
NA
NA
34”
1150
1770
2380
2780
3180
3580
3980
4370
4750
NA
NA
NA
NA
NA
NA
36”
1060
1790
2520
2670
3090
3510
3930
4350
5040
NA
NA
NA
NA
NA
NA
Notes:
1.)
Zone Dampers Should Be Sized Based On The Required Zone CFM. The Table Above Is
Calculated Based On 1000 FPM Velocity Through The Rectangular Damper. Zone Damper
Recommended Velocity Is 1000 – 1500 FPM. Select 1000 FPM or Less for Quiet Operation. For Other
Velocities, Use The Following Multipliers To Obtain The Correct CFM:
500 FPM = 0.5, 750 FPM =
0.75
,
1250 FPM = 1.25
,
1500 FPM = 1.5
,
2000 FPM = 2.0, 2250 FPM = 2.25
.
2.)
Bypass Dampers Should Be Selected for 60% to 70% of the HVAC Units Rated CFM Capacity.
Recommended Bypass Damper Velocity is 1750 – 2250 FPM.
firealarmresources.com
Summary of Contents for Auto-Zone Plus
Page 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 116: ...firealarmresources com...
Page 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Page 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Page 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Page 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...