Section 3
Auto-Zone Plus
3-36
Programming
Constant Volume AHU
Setpoints
Line 1 displays CVAHU Setpoints message for identification only.
Setpoint Screen #1
Setpoint Screen #2
CVAHU Setpoints
Occupied Setpoints
Cooling Setpt: 75
°
F
Heating Setpt: 72
°
F
The
Occupied Heating and Cooling Setpoints
are entered on
this screen. The Heating Setpoint should always be one degree
below the Cooling Setpoint, or the CVAHU will not accept the
new values.
Minimum
Default
Maximum
Cooling Setpoint
50°F
75°F
90°F
Heating Setpoint
50°F
72°F
90°F
CVAHU Setpoints
Unoccupied Setpoints
Cool Setup...: 10
°
F
Heat Setback.: -10
°
F
The
Unoccupied Heating and Cooling Setback
values are
entered on this screen. The Occupied Cooling Setpoint will be
increased by the Cooling Setback during Unoccupied Mode
and the Heating Setpoint will be decreased by the Heating
Setback.
Minimum
Default
Maximum
Cooling Setback
0°F
10°F
30°F
Heating Setback
0°F
-10°F
-30°F
firealarmresources.com
Summary of Contents for Auto-Zone Plus
Page 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 116: ...firealarmresources com...
Page 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Page 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Page 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Page 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...