Section 3
Auto-Zone Plus
3-40
Programming
Setpoint Screen #10
Setpoint Screen #11
CVAHU Setpoints
Cool Lockout.: 50
°
F
Heat Lockout.: 65
°
F
The mechanical heating and cooling can be locked out from
operating based on the Outdoor Air Temperature. If the
Outdoor Air Temperature is above the
Heating Lockout
, no
heating stages are allowed to activate or remain on if they are
already ON. If the Outdoor Air drops below the
Cooling
Lockout
, no cooling stages are allowed to activate or remain on
if they are already ON.
Minimum
Default
Maximum
Cool Lockout
-40°F
50°F
90°F
Heat Lockout
30°F
65°F
99°F
CVAHU Setpoints
Economizer Setpoints
Enable Setpt.:
50
°
F
Supply Setpt.:
55
°
F
If the CVAHU has been configured for Economizer Control,
this screen will appear.
The
Econo Enable setpoint
is the Outdoor Air or Wetbulb
Temperature that enables the Economizer to open past its
minimum position setpoint to control Supply Air Temperature.
The
Supply Setpt
is the Supply Air Temperature the
Economizer tries to maintain.
Minimum
Default
Maximum
Enable Setpt
-40°F
50°F
99°F
Supply Setpt
50°F
55°F
90°F
firealarmresources.com
Summary of Contents for Auto-Zone Plus
Page 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 116: ...firealarmresources com...
Page 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Page 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Page 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Page 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...