Auto-Zone Plus
Section 3
Programming
3-25
Configuration Screen #2
Configuration Screen #3
Configuration Screen #4
Heat Type.: Electric
Fan Mode.: Constant
Use Left/Right Arrow
The Zone Manager can control
electric or gas heating
. Each
type of heat has its own protection limits built into the Zone
Manager software.
The Zone Manager can also operate the fan in one of two
modes.
Constant
(Continuous) running during occupied hours.
Cycle
with heating or cooling during occupied hours.
The fan always cycles with heating or cooling during
unoccupied hours.
The Left/Right Arrow keys will toggle the current setting to the
opposite mode.
Economizer: Enabled
Use Left/Right Arrow
The Zone Manager has the ability to control the
Economizer
operation. To initiate Economizer operation, select Enabled. To
toggle between the two Economizer modes, use the Left/Right
Arrow keys.
HVAC Type.: Variable
Use Left/Right Arrow
The Zone Manager normally reads the
duct static pressure
and
controls it via the
bypass damper
. If your system does not
require static pressure control, select the Constant mode of
operation. To toggle between the HVAC types, use the
Left/Right Arrow keys.
firealarmresources.com
Summary of Contents for Auto-Zone Plus
Page 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 116: ...firealarmresources com...
Page 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Page 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Page 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Page 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...