Section 3
Auto-Zone Plus
3-26
Programming
Configuration Screen #5
Configuration Screen #6
Note
If no External Scheduler is used, enter a " 0 " for the Schedule!
Configuration Screen #7
BYPASS Act: Direct
Use Left/Right Arrow
Zone Manager
Uses Schedule #: 0
0 = Internal Clock
1-7 = External Clock
The Zone Manager normally uses its own
real-time clock
and
an
internal week schedule
to determine the
Occupied/Unoccupied mode of operation. The Zone Manager
does have the ability to use a
global broadcast
from another
scheduling device on the communications loop if a more
powerful schedule is required. If an external schedule is used,
the range of schedule numbers is 1 to 7.
Press < - > To Force
ReCalibration Of The
Static Pr. Sensor OR
ENTER to Skip This.
The Zone Manager only calibrates the
static pressure sensor
one time. This occurs on the initial powerup, so it is vital that
the sensor be attached before the system is ever powered up. If
you were not able to do this, or accidentally activated the
system before the sensor was available, you can force it to
restart and calibrate the Static Pressure Sensor by pressing the
Minus Sign key. If you don't need to re-calibrate, simply press
the Enter or Down arrow key to skip over this item.
The Zone Manager Bypass Damper normally opens in a
clockwise direction. If your bypass damper opens in a
counter-clockwise direction, select
reverse acting
instead
of
direct acting
operation. To toggle between the two
modes, use the Left/Right Arrow Keys.
firealarmresources.com
Summary of Contents for Auto-Zone Plus
Page 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 116: ...firealarmresources com...
Page 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Page 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Page 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Page 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...