Auto-Zone Plus
Section 2
Design Guide
2-31
Zone Controller Auxiliary Relay Board
Operation
Relay #1 - Parallel Fan
If the zone is in
cooling mode
or
vent mode
, the
parallel fan
can activate anytime the
zone temperature drops 0.5°F below the
heating setpoint
. It de-activates when the
temperature rises 0.5°F above the heating setpoint. The space temperature must be below
the AUX HEAT setpoint in the occupied mode before the Parallel Fan relay can be
energized.
Relay #2 - Box Heat
If the zone is in
cooling mode
or
vent mode
, the
box heat
can activate anytime the zone
temperature drops 1.5°F below the heating setpoint. It de-activates when the temperature
rises to within 1.0°F of the heating setpoint. Box heat is not allowed to activate in the
heating mode when there is hot air being supplied by the air handler. This output was
intended to allow zone re-heat while the Zone Manager is satisfying cooling demands in
other zones. The space temperature must be below the AUX HEAT setpoint in the
occupied mode before the Box Heat relay can be energized.
Relay #3 - Aux Heat
In the
occupied mode
, the
aux heat
can activate anytime the zone temperature is 0.5°F
below the
aux heat setpoint
. It de-activates when the temperature rises 0.5°F above the
aux heat setpoint. In the
unoccupied mode
, the aux heat uses the unoccupied heating
setpoint with the same deadband values mentioned above. This prevents the zone from
maintaining the same aux heat setpoint at night that it does during the daytime.
This output was intended to allow zone heating, to augment the normal heating mode and
also to allow a zone to attempt to satisfy its own heating needs before creating a heating
demand at the Zone Manager.
Relay #4 - Series Fan
The
series fan
runs anytime the main fan is running. This includes occupied and
unoccupied modes. In the unoccupied mode, the fan can only start when the zone damper
is closed. The controller checks to be sure the damper is closed before starting the fan.
firealarmresources.com
Summary of Contents for Auto-Zone Plus
Page 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 116: ...firealarmresources com...
Page 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Page 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Page 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Page 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...