Section 1
Auto-Zone Plus
1-20
Design Guide
Relay #1 - Parallel Fan
If the Zone is in cooling mode or vent mode, the parallel fan can activate anytime the
zone temperature drops 0.5
°
F below the heating setpoint. It de-activates when the
temperature rises above the heating setpoint. The space temperature must be below the
AUX HEAT setpoint in the occupied mode, before the Parallel Fan relay can be
energized.
Relay #2 - Box Heat
If the zone is in cooling mode or vent mode then the box heat can activate anytime the
zone temperature drops 1.5
°
F below the heating setpoint. It de-activates when the
temperature rises to within 1.0
°
F of the heating setpoint. Box heat is not allowed to
activate in the heating mode when there is hot air being supplied by the air handling unit.
This output was intended to allow zone re-heat while the Zone Manager is satisfying
cooling demands in other zones. The space temperature must be below the AUX HEAT
setpoint in the occupied mode, before the Box Heat relay can be energized.
Relay #3 - Aux Heat
In the occupied mode, the aux heat can activate anytime the zone temperature is 0.5
°
F
below the aux heat setpoint. It de-activates when the temperature rises 0.5
°
F above the
aux heat setpoint. In the unoccupied mode, the aux heat uses the unoccupied heating
setpoint with the same deadband values mentioned above. This prevents the zone from
maintaining the same aux heat setpoint at night that it does during the daytime.
This output was intended to allow zone heating to augment the normal heating mode and
also to allow a zone an attempt to satisfy its own heating needs before creating a heating
demand at the Zone Manager.
Relay #4 - Series Fan
The series fan runs anytime the main fan is running. This includes occupied and
unoccupied modes. The fan can only start running when the zone damper is closed, so it
determines that the damper is closed before starting the fan.
firealarmresources.com
Summary of Contents for Auto-Zone Plus
Page 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 116: ...firealarmresources com...
Page 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Page 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Page 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Page 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...