Auto-Zone Plus
Section 3
Programming
3-27
Zone Manager Setpoints
Control Setpoints
Setpoint Screen #1
Setpoint Screen #2
Cooling Lockout
If the outside air temperature drops 1
°
below this setpoint the
mechanical cooling is disabled. Cooling is re-enabled at 1
°
above this setpoint.
Heat1 Lockout
If the outside air temperature rises 1
°
above this setpoint the
first stage of heat is disabled. The first stage of heat is re-
enabled at 1
°
below this setpoint.
Heat2 Lockout
If the outside air temperature rises 1
°
above this setpoint the
any heating stages of heat are disabled. If the outside air
temperature drops 1
°
below this setpoint any heating stages
above the first are re-enabled.
DUCT STATIC SETPOINT
Static Press: 0.5"
This screen will be displayed to allow you to enter the
controlling duct
Static Pressure Setpoint
.
Minimum
Default
Maximum
Static Press
0.1"
0.5"
2.0"
LOCKOUT SETPOINTS
Cool Lockout: 0
°
Heat1 Lockout: 65
°
Heat2 Lockout: 45
°
The Mechanical Cooling and Heating Lockouts are entered on
this screen.
Minimum
Default
Maximum
Cool Lockout
-40°F
50°F
80°F
Heat1 Lockout
30°F
65°F
99°F
Heat2 Lockout
30°F
45°F
99°F
firealarmresources.com
Summary of Contents for Auto-Zone Plus
Page 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 116: ...firealarmresources com...
Page 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Page 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Page 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Page 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...