Section 4
Auto-Zone Plus
4-58
Start-Up and Troubleshooting
5.4
Pressure Sensor Voltage
Table 4-3:
Pressure Sensor Voltage
OE271 Duct Static Pressure Sensor
Pressure
@
Sensor
(“ W.C.)
Voltage
@
Input
(VDC)
Pressure
@
Sensor
(“ W.C.)
Voltage
@
Input
(VDC)
0.00
0.25
2.60
2.20
0.10
0.33
2.70
2.28
0.20
0.40
2.80
2.35
0.30
0.48
2.90
2.43
0.40
0.55
3.00
2.50
0.50
0.63
3.10
2.58
0.60
0.70
3.20
2.65
0.70
0.78
3.30
2.73
0.80
0.85
3.40
2.80
0.90
0.93
3.50
2.88
1.00
1.00
3.60
2.95
1.10
1.08
3.70
3.03
1.20
1.15
3.80
3.10
1.30
1.23
3.90
3.18
1.40
1.30
4.00
3.25
1.50
1.38
4.10
3.33
1.60
1.45
4.20
3.40
1.70
1.53
4.30
3.48
1.80
1.60
4.40
3.55
1.90
1.68
4.50
3.63
2.00
1.75
4.60
3.70
2.10
1.83
4.70
3.78
2.20
1.90
4.80
3.85
2.30
1.98
4.90
3.93
2.40
2.05
5.00
4.00
2.50
2.13
Notes:
1. Use the voltage column to check the Duct Static Pressure Sensor while connected to
powered controllers. Read voltage with meter set on DC volts. Place the “-”(minus) lead on
GND terminal and the “+”(plus) lead on the
0-5 pin terminal on (JP1) with the jumper
removed. Be sure to replace the jumper after checking.
firealarmresources.com
Summary of Contents for Auto-Zone Plus
Page 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 116: ...firealarmresources com...
Page 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Page 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Page 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Page 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...