Auto-Zone Plus
Section 4
Start-Up and Troubleshooting
4-57
5.3 Temperature Sensor Resistance
Table 4-2:
Temperature Sensor Resistance
Temperature
(
º
F)
Resistance
(Ohms)
Voltage @
Input (VDC)
Temperature
(
º
F)
Resistance
(Ohms)
Voltage @ Input
(VDC)
-10
93333
4.620
72
11136
2.695
-5
80531
4.550
73
10878
2.665
0
69822
4.474
74
10625
2.635
5
60552
4.390
75
10398
2.607
10
52500
4.297
76
10158
2.577
15
45902
4.200
78
9711
2.520
20
40147
4.095
80
9302
2.465
25
35165
3.982
82
8893
2.407
30
30805
3.862
84
8514
2.352
35
27140
3.737
86
8153
2.297
40
23874
3.605
88
7805
2.242
45
21094
3.470
90
7472
2.187
50
18655
3.330
95
6716
2.055
52
17799
3.275
100
6047
1.927
54
16956
3.217
105
5453
1.805
56
16164
3.160
110
4923
1.687
58
15385
3.100
115
4449
1.575
60
14681
3.042
120
4030
1.469
62
14014
2.985
125
3656
1.369
64
13382
2.927
130
3317
1.274
66
12758
2.867
135
3015
1.185
68
12191
2.810
140
2743
1.101
69
11906
2.780
145
2502
1.024
70
11652
2.752
150
2288
0.952
71
11379
2.722
Notes:
1. Use the resistance column to check the thermistor sensor while disconnected from the
controllers (not powered).
2. Use the voltage column to check sensors while connected to powered controllers. Read
voltage with meter set on DC volts. Place the “-”(minus) lead on GND terminal and the
“+”(plus) lead on the sensor input terminal being investigated.
If the voltage is above 5.08 VDC, then the sensor or wiring is “open.” If the voltage is
less than 0.05 VDC, the sensor or wiring is shorted.
firealarmresources.com
Summary of Contents for Auto-Zone Plus
Page 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Page 2: ...firealarmresources com...
Page 4: ...firealarmresources com...
Page 6: ...firealarmresources com...
Page 68: ...firealarmresources com...
Page 116: ...firealarmresources com...
Page 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Page 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Page 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Page 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...